Preliminary Technical Data
Line Voltage Sag Detection
In addition to the detection of the loss of the line voltage signal
(zero crossing), the ADE7566/ADE7569 can also be
programmed to detect when the absolute value of the line
voltage drops below a certain peak value for a number of line
V 2
VPKLVL[15:0]
ADE7566/ADE7569
cycles. This condition is illustrated in Figure 44.
VOLTAGE CHANNEL
FULL SCALE
SAGLVL [15:0]
PKV INTERRUPT
FLAG
READ RSTSTATUS
REGISTER
PKV RESET
LOW WHEN
RSTSTATUS
REGISTER
IS READ
SAG FLAG
SAGCYC [7:0] = 0x04
3 LINE CYCLES
SAG RESET LOW
WHEN VOLTAGE
CHANNEL EXCEEDS
SAGLVL [15:0] AND
SAG FLAG RESET
Figure 45. Peak Level Detection
Figure 45 shows a line voltage exceeding a threshold that is set
in the voltage peak register (VPKLVL[15:0]). The voltage peak
event is recorded by setting the PKV flag in the Interrupt Status
Figure 44. SAG Detection
Figure 44 shows the line voltage falling below a threshold that is
set in the SAG level register (SAGLVL[15:0]) for three line
cycles. The quantities 0 and 1 are not valid for the SAGCYC
register, and the contents represent one more than the desired
number of full line cycles. For example, when the SAG cycle
(SAGCYC[7:0]) contains 0x04, FSAG in the Power
Management Interrupt Flag SFR (IPSMF, 0xF8) is set at the end
of the third line cycle after the line voltage falls below the
threshold. If the SAG enable bit (ESAG) in the Power
Management Interrupt Enable SFR (IPSME, 0xEC) is set, the
8052 core has a pending power supply monitoring interrupt.
The PSM interrupt stays active until the ESAG bit is cleared (see
the Power Supply Monitor Interrupt (PSM) section).
In Figure 44, the SAG flag (FSAG) is set on the fifth line cycle
after the signal on the voltage channel first dropped below the
threshold level.
Sag Level Set
The 2-byte contents of the SAG level register (SAGLVL, 0x14)
are compared to the absolute value of the output from LPF1.
Therefore, when LPF1 is enabled, writing 0x2038 to the SAG
level register puts the SAG detection level at full scale (see
Figure 36). Writing 0x00 or 0x01 puts the SAG detection level at
0. The SAG level register is compared to the input of the ZX
detection, and detection is made when the contents of the SAG
level register are greater.
Peak Detection
The ADE7566/ADE7569 can also be programmed to detect
when the absolute value of the voltage or current channel
exceeds a specified peak value. Figure 45 illustrates the behavior
of the peak detection for the voltage channel. Both voltage and
current channels are monitored at the same time.
Register 3 SFR (MIRQSTH, 0xDE). If the PKV enable bit is set
in the Interrupt Enable Register 3 SFR (MIRQENH, 0xDB), the
8052 core has a pending ADE interrupt. Similarly, the current
peak event is recorded by setting the PKI flag in Interrupt Status
Register 3 SFR (MIRQSTH, 0xDE). The ADE interrupt stays
active until the PKV or PKI status bit is cleared (see the Energy
Measurement Interrupts section).
Peak Level Set
The contents of the VPKLVL and IPKLVL registers are compared
to the absolute value of the voltage and current channels 2 MSBs,
respectively. Thus, for example, the nominal maximum code
from the Current Channel ADC with a full-scale signal is
0x28F5C2 (see the Current Channel ADC section). Therefore,
writing 0x28F5 to the IPKLVL register puts the current channel,
peak detection level at full scale and sets the current peak
detection to its least sensitive value. Writing 0x00 puts the
current channel detection level at 0. The detection is done by
comparing the contents of the IPKLVL register to the incoming
current channel sample. The PKI flag indicates that the peak level is
exceeded. If the PKI or PKV bit is set in the Interrupt Enable
Register 3 SFR (MIRQENH, 0xDB), the 8052 core has a
pending ADE interrupt.
Peak Level Record
Each ADE7566/ADE7569 records the maximum absolute value
reached by the voltage and current channels in two different
registers, IPEAK and VPEAK, respectively. Each register is a 24-
bit unsigned register that is updated each time the absolute
value of the waveform sample from the corresponding channel
is above the value stored in the VPEAK or IPEAK register. The
contents of the VPEAK register correspond to the maximum
absolute value observed on the voltage channel input. The
contents of IPEAK and VPEAK represent the maximum
absolute value observed on the current and voltage input,
respectively. Reading the RSTVPEAK and RSTIPEAK registers
clears their respective contents after the read operation.
Rev. PrA | Page 47 of 136
相关PDF资料
ADE7752BARWZ-RL IC ENERGY METERING 3PHASE 24SOIC
ADE7755ARSZ IC ENERGY METERING 1PHASE 24SSOP
ADE7757ARNZRL IC ENERGY METERING 1PHASE 16SOIC
ADE7758ARWZRL IC ENERGY METERING 3PHASE 24SOIC
ADE7761AARSZ-RL IC ENERGY METERING 1PHASE 20SSOP
ADE7761BARSZ-RL IC ENERGY METERING 1PHASE 20SSOP
ADE7768ARZ-RL IC ENERGY METERING 1PHASE 16SOIC
ADE7769ARZ-RL IC ENERGY METERING 1PHASE 16SOIC
相关代理商/技术参数
ADE7569ASTZF162 制造商:AD 制造商全称:Analog Devices 功能描述:Single-Phase Energy Measurement IC with 8052 MCU, RTC, and LCD Driver
ADE7569ASTZF16-RL 功能描述:IC ENERGY METER 1PHASE 64-LQFP RoHS:是 类别:集成电路 (IC) >> PMIC - 能量测量 系列:- 产品培训模块:Lead (SnPb) Finish for COTS Obsolescence Mitigation Program 标准包装:2,500 系列:*
ADE7569ASTZF16-RL2 制造商:AD 制造商全称:Analog Devices 功能描述:Single-Phase Energy Measurement IC with 8052 MCU, RTC, and LCD Driver
ADE7751 制造商:AD 制造商全称:Analog Devices 功能描述:Energy Metering IC with On-Chip Fault Detection
ADE7751AAN-REF 制造商:AD 制造商全称:Analog Devices 功能描述:Energy Metering IC with On-Chip Fault Detection
ADE7751AN 制造商:Analog Devices 功能描述:Energy Measurement 24-Pin PDIP 制造商:Analog Devices 功能描述:ENERGY MEASUREMENT 24PDIP - Bulk 制造商:Rochester Electronics LLC 功能描述:PRODUCT TO FREQUENCY CONVERTER I.C. - Bulk
ADE7751ARS 制造商:Rochester Electronics LLC 功能描述:PRODUCT TO FREQUENCY CONVERTER I.C. - Bulk 制造商:Analog Devices 功能描述:IC ENERGY METER
ADE7751ARSRL 制造商:Analog Devices 功能描述:Energy Measurement 24-Pin SSOP T/R 制造商:Analog Devices 功能描述:IC ENERGY METER